Add to Cart
1. 11KV 33KV box type compact transformer substation distribution substation
2. Environmental Information
-Sealed tank construction
-Special waste disposal considerations
-Insulation temperature limit: 120 °C
-Temperature rise: 65 °C (standard); 55 °C or 55/65 °C (optional)
Special Design Options
-Special sound requirements
-Special altitude requirements
-Retrofit designs
-Higher efficiency requirements
3. Technical data
Item | Unit | HV Department | Transformer | LV Department |
Rated Voltage | kV | 12/24/36 | (12/24/36)/0.4 | 0.4 |
Rated Current | A | 630 | 3/75-150/3750 | Less than 4000 |
Frequency | Hz | 50 | ||
Rated Capacity | KVA | 50-2500 | ||
Pfr Withstand | kV | 42/50/70/95 | 2.5 | |
BIL | kV | 72/125/170/185 | / | |
Crust Protection Grade | | IP23 | Oil type 55, Dry type 65 | IP23 |
Appearance Dimensions | mm | According to primacy wiring circuit schema |
Item | Unit | HV Department | Transformer | LV Department |
Rated Voltage | kV | 40.5 | 40.5/12/0.69/0.4 | 12/6.3/0.69/0.4 |
Rated Current | A | Less than 1250 | / | Less than 4000 |
Frequency | Hz | 50 | ||
Rated Capacity | KVA | 1250-20000 | ||
Pfr Withstand | kV | 70/95 | 42/2.5(Auxiliary) | |
BIL | kV | 170/185 | 75 | |
Crust Protection Grade | | IP23 | Oil type 55, Dry type 65 | IP23 |
Appearance Dimensions | mm | According to primacy wiring circuit schema |
6. Delivery